Voltage Drop Calculator
Estimate resistive voltage drop from current, one-way conductor length, conductor area, material and assumed conductor temperature. The calculator distinguishes a two-wire DC or single-phase circuit from a balanced three-phase circuit, while deliberately excluding reactance and installation-code compliance.
By Dr. Hassan Khames EliwaLast updated
Result
- Drop percentage
- 1.1994%
- Estimated receiving voltageResistive approximation; a negative result means the assumed operating point is not feasible.
- 227.2414 V
- One conductor resistance
- 0.137928 Ω
How it works
Resistance comes before voltage drop
A conductor resistance is resistivity × length ÷ cross-sectional area. Area is entered in square millimetres for both length-unit choices; imperial mode changes feet to metres and does not accept AWG sizes. Use the actual conductor area from a reliable specification rather than substituting cable outside diameter or an approximate gauge number.
This model assumes annealed copper resistivity of 0.017241 Ω·mm²/m at 20 °C and aluminum resistivity of 0.028264 Ω·mm²/m at that reference temperature. It applies a linear temperature coefficient of 0.00393 per °C for copper or 0.00403 per °C for aluminum. These are explicit conventional modeling constants, not guaranteed values for every conductor alloy, strand arrangement or product.
The adjustment is resistivity at temperature = reference resistivity × [1 + coefficient × (temperature − reference temperature)]. The temperature field describes the conductor, not necessarily the surrounding air. Load current, installation method and ambient conditions influence conductor temperature, but this tool does not solve that thermal problem. Its accepted temperature range limits an approximate calculation rather than certifying insulation suitability.
Use one-way route length
For DC and single-phase two-wire circuits, drop equals twice current times the resistance of one conductor. Enter the route length from source to load; the model adds the return path. It assumes equal outgoing and return conductor areas. An earth-return circuit or an undersized neutral is not represented by that assumption.
For balanced three-phase circuits, the multiplier is the square root of three rather than twice. Enter line current and line-to-line supply voltage. The answer is an approximate line-to-line drop with the resistive, unity-power-factor simplification. Unbalance, significant reactance, motor starting and non-unity power factor require a more complete circuit model.
Read the percentage in context
Drop percentage is calculated against the entered supply voltage. Estimated receiving voltage is supply minus modeled drop. If the result becomes negative, the assumed current and circuit are not a feasible operating point; the negative value is a warning about the inputs, not a physical prediction of reversed voltage. No automatic pass threshold is imposed because requirements depend on jurisdiction, load and installation context.
Worked example
Scenario A: copper two-wire run
Use DC, copper, metres, one-way length 20 m, area 2.5 mm², current 10 A, supply 230 V and conductor temperature 20 °C. One-conductor resistance is 0.137928 Ω. Drop is 2.7586 V, or 1.1994%, and receiving voltage is 227.2414 V. Single-phase mode gives the same result under the stated resistive assumptions.
Scenario B: balanced aluminum feeder
Choose three-phase, aluminum, length 50 m, area 16 mm², current 30 A, supply 400 V and temperature 20 °C. Resistance is 0.088325 Ω per conductor. Displayed drop is 4.5895 V, percentage is 1.1474%, and receiving voltage is 395.4105 V. This calculation is not an ampacity check or approval to install that conductor.
Expert tips
Common mistakes
- Do not double the entered route length for a two-wire circuit. The formula already includes the return conductor, so doubling the length again doubles the modeled drop.
- Do not interpret a low voltage-drop percentage as proof of electrical safety. Fault protection, thermal limits, bonding and disconnection requirements are separate checks for qualified design and installation.
- Do not enter a cable diameter where conductor area is requested. Nor should you assume aluminum and copper of equal area have equal resistance; the material selection changes the model.
Frequently asked questions
Does imperial mode accept AWG?
No. Only route length switches to feet. Cross-sectional area remains in mm², so obtain an appropriate area from the conductor specification before calculating.
Why is AC simplified?
AC impedance includes reactance, and power factor affects the voltage relationship. This resistive model is useful for screening but cannot stand in for a detailed feeder calculation.
Can current or length be zero?
Yes. Either gives zero modeled drop with otherwise valid inputs. Area and supply voltage must remain positive to avoid undefined resistance or percentage calculations.
Is temperature the ambient temperature?
Not necessarily. Enter the estimated conductor operating temperature. Assuming ambient equals conductor temperature under load can understate resistance; this tool does not estimate heating.
Does the answer meet code?
The calculator makes no compliance judgment. Review applicable rules and manufacturer data with a qualified electrical professional, particularly for protection, allowable temperature and installation conditions.
Related calculators
Related guides
MathPercentages people get wrong: change, difference and pointsThe denominator determines the answer. Learn to distinguish percentage change, symmetric difference and percentage-point movements.14 November 2026 · 7 min read
MathStandard deviation without the jargonThe average tells you the centre. Standard deviation helps describe the spread, provided you know what the data represents.14 November 2026 · 7 min readSources and standards
About the author
Dr. Hassan Khames Eliwa holds a PhD in Construction & Built Environment and has more than 20 years of international project controls experience. He is Director of Eliwa Project Controls Limited in Auckland and founder of PMMilestone.org and PMMilestone.com.
Buy me a coffee